An appliance rating plate is the label or stamped plate that tells you who made the item, what it is, and how it is built to be powered. With an appliance rating plate explained in plain terms, a test and tag visit gets easier: the plate gives you the make, model and serial number for the register, the voltage and power ratings, and, most importantly, whether the item is Class I or Class II. That last detail decides which tests you do.
This guide walks through each marking you're likely to see on equipment in Australia and New Zealand, what it means for the test, and what to record so the item can be found and identified again next year.
General information only. Follow AS/NZS 3760, the instructions for your test instrument and your state or territory regulator's guidance. When a marking is unclear, treat the item with caution rather than guessing.
Where to find the rating plate
Most plates sit somewhere out of the way: under a kettle or toaster, on the back of a monitor or printer, on the side of a power tool's motor housing, or on the plug pack of a laptop charger. On larger machines, look near where the supply cord enters. Some items carry the details on a moulded panel or a printed sticker instead of a metal plate.
If you can't find one at first, check the battery bay, inside a lid or door, and the underside. Wipe off grease or dust before you read it.
What each marking means
Not every plate shows everything below, and the layout varies by manufacturer. These are the markings you'll see most often.
| Marking | What it looks like | Why it matters on a test |
|---|---|---|
| Make and model | A brand name and a model or type number | Identifies the item in your register and on certificates |
| Serial number | Often labelled S/N, SER or No. | Tells two identical items apart |
| Rated voltage | For example 220–240 V~ or 230 V | Shows the item is built for Australian and New Zealand mains |
| Frequency | 50 Hz, or 50/60 Hz | Mains here is 50 Hz |
| Power or current | Watts (W) for appliances, amps (A) for leads and powerboards | Helps you describe the item and spot one used beyond its rating |
| Class II symbol | A square inside a square | No earth continuity test is needed |
| RCM | A triangle with a tick inside a circle | The supplier's compliance mark |
| Older approval number | For example Q, NSW or V followed by numbers | An approval from before the RCM, still seen on older stock |
| IP code | IP followed by two characters, such as IPX4 | Protection against solids and water |
Make, model and serial number
These are the details that make an item findable. Two staff kettles of the same model only become separate records when you capture the serial number or give each its own asset code, or both. Type serial numbers exactly as shown, including leading zeros and letters, because they're easy to mangle when the data moves between systems later. Our guide to cleaning equipment data before an import covers the common ways serial numbers and codes go wrong.
Voltage and frequency
The symbol after the voltage tells you the supply type: ~ means AC, and a solid line over a dashed line means DC. Most mains equipment here shows a range like 220–240 V~ 50 Hz, or 230 V~ 50 Hz.
A plate that only shows 110–120 V or 60 Hz suggests the item was made for another market, such as a piece of equipment bought overseas and used with a travel adaptor. That doesn't tell you on its own whether it is safe, but it's worth noting and raising with the client.
Watts and amps
Appliances usually show power in watts. Powerboards, extension leads and cord sets usually show a current rating in amps, commonly 10 A. Record the rating in the item's description, such as "2400 W fan heater" or "10 A 4-outlet powerboard", so the item is easy to recognise on the next visit.
The Class II symbol: the marking that changes your test
Class II equipment is double insulated: it relies on two layers of insulation, or reinforced insulation, rather than an earth connection. It's marked with a square inside a square, the international symbol IEC 60417-5172, usually placed near the supply details on the rating plate (see the reference from manufacturer Philips).
The class matters because the tests differ. WorkSafe ACT lists what in-service testing should include, where applicable (WorkSafe ACT):
- an external inspection of the equipment and its supply cord
- a protective earth continuity test for Class I equipment, powerboards and cord sets
- an insulation test, by measuring insulation resistance or leakage current
- a polarity check on cord sets with rewireable plugs and extension sockets
So a Class II hair dryer gets the inspection and an insulation test, but no earth continuity test. A Class I item, which has exposed metal connected to earth through the plug's earth pin, needs the earth continuity test as well.
Class I equipment usually has no class symbol at all. Common practice is to treat an item as Class I unless the plate shows the double square. Don't decide the class from the plug alone, and don't assume an item is double insulated because it has a plastic case.
Class III equipment runs from a safety extra-low voltage supply, such as a device charged by a plug pack. The item you test is usually that power supply, which carries its own plate.
The RCM and older approval marks
The Regulatory Compliance Mark (RCM) is a triangle with a ticked circle inside it. According to the national Electrical Equipment Safety System, in-scope electrical equipment offered for sale by registered suppliers must carry it, and the authority to apply it sits with the Responsible Supplier (EESS). Energy Safe Victoria tells buyers to look for the RCM on electrical appliances (Energy Safe Victoria).
Older equipment may instead show a state approval number. The WA Government lists marks such as Q, NSW, N, V and ESV followed by numbers, and suggests searching the model number on the EESS website to confirm an approval (WA Government).
Keep the RCM in perspective. It relates to the supplier and the point of sale. It says nothing about the condition of the item in front of you today, which is what your inspection and tests are for.
IP codes
An IP code shows how well the enclosure keeps out solid objects and water. The first character covers solids and the second covers water, and an X means that part wasn't rated. You'll see them on outdoor gear, pressure washers and some site equipment. They don't change your tests, but they're a useful detail for the description.
What to record from the plate
You don't need every marking in the register. These are the details that earn their place:
- Make and model. For the description, certificates and finding the item again.
- Serial number. Wherever there is one.
- Equipment class. Class I, Class II, cord set or RCD, using one spelling every time.
- Rating. Watts or amps, in the description or its own field.
- A photo of the plate. If your software allows it. It settles arguments about which item was tested.
Add your own asset code and the location as well. Our guide to test and tag records covers what else belongs in the register and how long to keep it.
When the plate is missing or unreadable
Plates get painted over, worn smooth or peeled off. When that happens:
- Record what you can see. The make from the case, a clear description and the location.
- Don't guess the class. If you can't confirm the item is double insulated, treat it as Class I and test it that way.
- Note it. Write "rating plate unreadable" in the notes so the next technician isn't left wondering.
- Raise it with the client if the item can't be identified at all. Whether it stays in service is their decision, informed by your inspection and test results.
Reading plates faster on site
Typing a long serial number off a dusty plate is one of the slowest parts of adding a new item, and it's where typos creep in. In Koalaris, you can take a photo of the plate and Lyra AI prefills the item's name, make, model, serial number, voltage, wattage and appliance class. Anything it isn't sure of, such as a worn serial number or a class it couldn't confirm, is flagged for you to check. Nothing is saved until you confirm every field, and Lyra AI never sets pass or fail. With no signal, the photo waits on your phone and is read once you're back online. The rating plate tutorial shows it in 22 seconds.
For a good photo, fill the frame with the plate, shoot it square on, and tilt the phone slightly to avoid glare from a torch or the sun.
Frequently asked questions
What does the square inside a square mean on an appliance?
It's the Class II symbol. The item is double insulated and doesn't rely on an earth connection, so it doesn't get an earth continuity test. It still needs a visual inspection and an insulation test.
Is an appliance without an RCM unsafe?
Not necessarily. Older equipment may carry an earlier state approval number instead, and the RCM only relates to how the item was supplied. Your inspection and tests show its condition now. If a client is unsure whether an item was ever approved, they can search its model number on the EESS website.
What if an item has no rating plate?
Record a clear description, the make if visible, and the location, and note that the plate is missing. If you can't confirm it's Class II, test it as Class I.
Do I need to record the serial number?
It isn't the only way to identify an item, but it's the most reliable way to tell identical items apart. Record it whenever there is one, alongside your own asset code.
Start your register with the plate
Koalaris's Free plan has no card, no end date and no limit on items, and it includes 10 Lyra AI rating-plate scans a month. Solo is $29 a month with 30 scans, and Pro has no monthly count.
Keep reading
GuidesTest and tag for events and markets: a guide for operators
Test and tag for events and markets: what organisers and councils ask stallholders for, AS/NZS 3002, leads and RCDs, and how operators run event-day testing.
How-toTest and tag register template (free CSV) and how to fill it in
Download a free test and tag register template in CSV. What each column means, the extra columns worth adding, and how to stop Excel breaking your tag numbers.
GuidesChanging test and tag software without losing your history
Changing test and tag software? When to switch in the retest cycle, how to keep your tags, asset numbers and old certificates, and what to tell your clients.
See your register the way Lyra sees it.
Start free, for as long as you like. No card needed.